深圳市知用电子有限公司
ShenZhen ZhiYong Electronics Co., Ltd.
CTA60 60A /800kHz
CTA60 60A /800kHz

Primary current, measuring range (IPM) ±60A

Accuracy 0.03%

浏览次数:603
说明书: 产品说明书

1. Summary

CTA series is the ultra-accuracy transducer that can measure both DC and AC. Its current range covers from 60A to 2000A with precision of 0.03% and 800 kHz bandwidth. By using Flux-gate technic, the CTA series realized high accurate measurement, excellent linearity, low DC offset, lower temperature drift, low insertion loss, high immunity to external field and low noise.

 

CTA series transducer includes CTA60(60A),CTA200(200A),CTA400(400A),CTA700(700A)  CTA1000(1000A) and CTA20002000A. CTA60 ,CTA200,CTA400 have measurement aperture of 26mm; CTA700,CTA1000 have measurement aperture of 30mm and CTA2000 have measurement aperture of 70mm. CTA series transducers have standard 9 pin D-Sub male interface and LED Indicator, making the system not only easy to use but also reliable.


1. Specification
Test temperature: 25℃; Voltage Supplied: ±Uc =±15V

TypeCTA60
Primary nominal continuous
Direct current  (IPN DC)
60A
Primary nominal rms current (IPN) 42A
Primary current, measuring range
(IPM)
±60A
Conversion ratio KN 1:600
Secondary current (IS) ±100mA
Accuracy (DC,50/60Hz sine wave) ≤±(0.03% of the readings +30uA)
Bandwidth(±3dB) 800kHz
Measuring resistance over
operating current temperature and
supply voltage range
RM min RM max
0 60Ω
Figure 1
Overload capability @ pulse of
100ms
±300A
Supply voltage ±15V(±5%)
Supply current ≤80mA+IS
Rated operational
voltage
RMS(IEC61010-1)
Basic insulation 2000V
Reinforced insulation 600V
Max measurement aperture 26mm
Second interface D-Sub-9Pin
Fastening screws and tighening
torque
M4 steel screw *4;2.8Nm
M5 steel screw *2;3.7Nm