深圳市知用电子有限公司
ShenZhen ZhiYong Electronics Co., Ltd.
CTA2000B(2000A/DC~140kHz)
CTA2000B(2000A/DC~140kHz)

Bandwidth(±3dB)  140kHz


 

浏览次数:0
说明书: 产品说明书

1. Summary

CTA series is the ultra-accuracy transducer that can measure both DC and AC. Its current range covers from 60A to 2000A with precision of 0.03% and 800 kHz bandwidth. By using Flux-gate technic, the CTA series realized high accurate measurement, excellent linearity, low DC offset, lower temperature drift, low insertion loss, high immunity to external field and low noise.


1. Specification

Test temperature: 25; Voltage Supplied: ±Uc =±15V

Type

CTA2000B

Primary nominal continuous

Direct current  (IPN DC)

2000A

Primary nominal rms current (IPN)

2000A

Primary current, measuring range (IPM)

±2000A

Conversion ratio KN

1:2000

Secondary current (IS)

±1000mA

Accuracy (DC,50/60Hz sine wave)

≤±(0.03% of the readings +30uA)

Bandwidth(±3dB)

140kHz

Measuring resistance over

operating current temperature and

supply voltage range

RM min

RM max

0

1Ω

FIG.6

Overload capability @ pulse of 100ms

±10kA

Supply voltage

±15V(±5%)

Supply current

150mA+IS

Rated operational

voltage  

RMSIEC61010-1

Basic insulation

1000V

Reinforced insulation

300V

Max measurement aperture

80mm

Second interface

D-Sub-9Pin

Fastening screws and tightening

torque

M5 steel screw *43.7Nm

image.png